- Product description
-
Product descriptionSystem solution, type 2, with MC4 connector for photovoltaic inverter with 2 separate MPP trackers
• Varistor arrester, connectable with cut-off unit in error-resistant Y circuit to VDE 0100-712 (50539-12)
• Low DC voltage protection level: < 4.0 kV (Voc max = 1,000V DC with V20-C/0-500PV)
• One PV string input (MC4 plug connector) at one MPP inverter input, up to 30A DC per terminal
• Pre-mounted in polycarbonate housing (IP66), UV-resistant for use outside
For DC protection of the inverter of photovoltaic systems.
If there is a danger of condensation forming through wind, ice, temperature or sunlight, further measures may be necessary!
-
- Technical data
-
Connectivity options
Anschlussart Generatoranschlusskasten MC4 CO2 Footprint (GWP) Cradle-to-Gate 5,8233 kg CO2e / 1 Piece Colour Light grey; RAL 7035 Conductor cross-section, flexible (fine-wire), min. 25 mm² Conductor cross-section, rigid (single-wire/multiwire), max. 35 mm² DC network form yes Depth 113 mm Dimension 1000V DC Entries per MPPT 1 Equipped with load-break switch no Exits per MPPT 1 Height 190 mm Housing material surge protection components PC Installation type Pre-mounted in the housing IT network form no Lightning protection zone LPZ 1→2 Max. Input current per string 30 A Max. Input voltage DC 1000 V Max. mains-side overcurrent protection 125 Max. Output current 30 A Max. PV voltage 1000 V Maximum back-up fuse 125 A Maximum continuous voltage DC 1000 V Maximum discharge current (8/20 μs) 40 kA Monitoring function no Network form DC Nominal discharge current (8/20 µs) 20 kA Number of cable entries 4 Number of inputs 1 Number of MPPTs 2 Number of string inputs 1 Operating temperature, max. 80 °C Operating temperature, min. -40 °C Other network form no Permitted temperature range, max. 80 °C Permitted temperature range, min. -40 °C Pole number 3 Protection rating IP66 Protection rating IK code IK05. Remote signalling no Response time <25 ns Signalling on device Visual SPD to EN 61643-11 Type 2 SPD to IEC 61643-1 Class II String fuse Without Test class, type 1 no Test class, type 2 yes Test class, type 3 no TN network form no TN-C network form no TN-C-S network form no TN-S network form no TT network form no Type of entry MC4 Version for For two MPP trackers and with MC4 connection Width 240 mm - All types
- Downloads
-
Data sheet PVG-C1000S110 / 5088556 , 0.36MB , pdfEU declaration of conformity PVG-C1000S110 / 5088556 , 0.11MB , pdfREACH Declaration of conformity PVG-C1000S110 / 5088556 , 0.12MB , pdfRoHS Declaration of conformity PVG-C1000S110 / 5088556 , 0.13MB , pdfLabel approval VDE test report V20-PH , 0.05MB , pdfLabel approval DEKRA test report V20-PH , 0.08MB , pdfSelection aid Surge protection for photovoltaic systems , 1.31MB , pdfSelection aid Selection aid, surge protection , 2.00MB , pdf