Combined protection device 3in1 for CCTV camera systems

Item no. 5081072 | EAN 4012196676972

  • 5-year warranty
  • Transition from LPZ 0 to LPZ 2
  • Communautés Européennes, EC declaration of conformity according to EC directives
  • TV applications
  • Installation electrotechnical expertise

Combination protection device for coaxial TV/camera systems

• Protection of power and data interfaces in a single device
• In aluminium housing
• Simple mounting with adapter
• Two-stage protection circuit
• Three-pole power connection for the power interface
• With LED operation display (OS)
• Incl. DIN rail fastening set


Application: Protection of CCTV, video signals, cameras and/or TV systems

All types

All types

Types Maximum
continuous voltage
(L-N)
Maximum
discharge current
(8/20 μs)
Item no. Quantity SSU
PND-3in1-C-OS 255 V 10 kA 5081072
1 piece
Combined protection device 3in1 for CCTV camera systems
Combined protection device 3in1 for CCTV camera systems

Combined protection device 3in1 for CCTV camera systems

Item no. 5081072

Data sheet, 0.30MB, pdf
Download

Technical data

Temperature range -20 - +80 °C
Installation type Installation
Protection rating IP20
Earthing via: Connection cable / DIN rail
Lightning protection zone LPZ 1→3
SPD to IEC 61643-11 Class II+III
SPD to EN 61643-11 Type 2+3
Maximum continuous voltage (L-N) 255 V
Rated current 16 A
Protection level <1,3 kV
Idle voltage 10 kV
Nominal discharge current (8/20 µs) 5 kA
Maximum discharge current (8/20 μs) 10 kA

Dimensions

Length 122.5 mm
Width 100 mm
Height 37.1 mm

Data

Maximum continuous voltage AC 5.65 V
Maximum continuous voltage DC 8 V
SPD to IEC 61643-21 Class I+II / D1+C2
Category Type 1+2 / D1+C2
Impulse durability wire-wire C2: 10 kV / 5 kA (8/20µs)
Impulse durability wire-earth C2: 10 kV / 5 kA (8/20µs)
Impulse current (10/350) 1 kA
Protection level wire-earth <450 V
Protection level wire-wire <65 V
Frequency range 0-100 MHz
Frequency range 0 - 100 MHz
Cut-off frequency 100 MHz
Screen connection Yes
Screening Direct
Testing standard IEC 61643-21

Video

Maximum continuous voltage AC 5.65 V
Maximum continuous voltage DC 8 V
SPD to IEC 61643-21 Class I+II / D1+C2
Category Type 1+2 / D1+C2
Impulse durability wire-earth C2: 10 kV / 5 kA (8/20µs)
Impulse durability wire-wire C2: 10 kV / 5 kA (8/20µs)
Impulse current (10/350) 1 kA
Protection level wire-wire <90 V
Protection level wire-earth <150 V
Frequency range 0-100 MHz
Frequency range 0 - 100 MHz
Cut-off frequency 100 MHz
Screen connection Yes
Screening Direct
Testing standard IEC 61643-21
Invitation to tender text

Invitation to tender text

PND-3in1-C-OS / 5081072
Download
Downloads

Data sheet

PND-3in1-C-OS / 5081072, 0.30MB, pdf
Download

Catalogues & Flyers

Surge protection for closed-circuit television systems (CCTV), 1.42MB, pdf