Protection set MCD + V20 3-pole
Type PS3-B+C TNC | Item no. 5089754 | EAN 4012195405528




Item no. / Type
5089754 / PS3-B+C TNC
Protection rating
IP20
Pole version
3
Smallest selling unit: 1 piece
1piece
Description
Protection set, lightning and surge arrester combination, type 1+2
• For lightning protection equipotential bonding to VDE 0185-305 (IEC 62305)
• Lightning current arresting capacity to 50 kA (10/350) per pole
• Arrester, connectable, incl. connecting bridges, labelled connection terminals
• Encapsulated, non-extinguishing arrester for use in distributor housings
Application: Mobile telecommunications systems and industrial systems with special requirements.
• For lightning protection equipotential bonding to VDE 0185-305 (IEC 62305)
• Lightning current arresting capacity to 50 kA (10/350) per pole
• Arrester, connectable, incl. connecting bridges, labelled connection terminals
• Encapsulated, non-extinguishing arrester for use in distributor housings
Application: Mobile telecommunications systems and industrial systems with special requirements.
Technical data
Technical data
Pole number | 3 |
---|---|
Network form | TN-C |
Blow-out | no |
Signalling on device | Visual |
Protection rating | IP20 |
Maximum continuous voltage (L-N) | 255 V |
Lightning surge current (10/350) | 100 kA |
Remote signalling | no |
Nominal voltage AC (50/60 Hz) | 230 V |
Lightning surge current (10/350 μs) | 50 kA |
Maximum continuous voltage AC | 255 V |
Nominal discharge current (8/20 µs) | 50 kA |
Pole version | 3 |
Max. mains-side overcurrent protection | 125 |
Short-circuit resistance for max. mains-side overcurrent protection | 25 kA |
Version for | 3-pole; 255 V |
Operating temperature, max. | 85 °C |
Operating temperature, min. | -40 °C |
SPD to IEC 61643-1 | Class I+II |
SPD to EN 61643-11 | Type 1+2 |
Lightning protection zone LPZ | 0→2 |
Maximum discharge current (8/20 μs) | 100 kA |
Follow current quenching capacity (eff) [N-PE] | 25 kA |
Short-circuit resistance | 25 kA |
Response time | <25 ns |
Maximum back-up fuse | 125 A |
Permitted temperature range, max. | 85 °C |
Permitted temperature range, min. | -40 °C |
Dimension | 255V |
CO2 Footprint (GWP) Cradle-to-Gate | 7,7517 kg CO2e / 1 Piece |
Connectivity options
Arrester surge current (8/20 µs) [total] | 100 kA |
---|---|
Conductor cross-section, rigid (single-wire/multiwire), min. | 10 mm² |
Downloads
0 selected
Data sheet (1)
Catalogues & Flyers (2)
Declarations (2)
Certificates (2)
Instructions and Aid (2)
Product images (3)
Tender specifications (2)
Variants
Type
Protection rating
Maximum continuous voltage AC
Pole version
Item no.
PS3-B+C TNC
IP20
255
3
5089754
PS3-B+C TNC
Item no.
5089754
Protection rating
IP20
Maximum continuous voltage AC
255
Pole version
3