Combination protection device TD-4/I for ISDN and DSL systems

Item no. 5081690 | EAN 4012196034352

5081690 / TD-4/I
4
120
170
RJ11
Product description

Product description

Data cable protection device for telecommunications equipment

• Low protection level at a high current load
• "Push-in" terminals for quick installation
• Bandwidth-optimised for secure transmission
• Surface mounting
• Visual function display
Application: DSL systems, IP connections, ISDN or analogue telecommunications
  • 5-year warranty
  • Communautés Européennes, EC declaration of conformity according to EC directives
  • Protection rating IP 54
  • Transition from LPZ 0 to LPZ 3
  • Integrated Service Digital Network, ISDN applications
  • Digital Subscriber Line, DSL applications
  • Analogue telecommunication
  • Installation electrotechnical expertise
Technical data

Technical data

Arrestor monitoring no
Cable type for surge protection devices Telecommunications line
Capacity (wire-earth) <10 pF
Capacity (wire-wire) <50 pF
Colour White
Connection cross-section, flexible, max. 0,75 mm²
Connection cross-section, flexible, min. 0,14 mm²
Connection cross-section, multi-wire, max. 0,75 mm²
Connection cross-section, multi-wire, min. 0,14 mm²
Connection cross-section, rigid, max. 0,75 mm²
Connection cross-section, rigid, min. 0,14 mm²
Cut-off frequency 100 MHz
Dimension 170V
Explosion-tested version no
Impulse durability wire-earth C2: 18 kV / 9 kA (8/20µs)
Impulse durability wire-wire C2: 18 kV / 9 kA (8/20µs)
Insertion loss ≤3 dB
Insulation resistance >1 MΩ
Kategorie Type 1+2+3 / D1+C2+C1
Lightning impulse current 2,5 kA
Lightning protection zone LPZ 0→3
Material Plastic
Maximum continuous voltage AC 120
Maximum continuous voltage DC 170
Nominal load current AC 0,14
Nominal load current DC 0,2 A
Number of poles 4
Permitted temperature range, max. 80 °C
Permitted temperature range, min. -40 °C
Plug-in system RJ11
Protection level wire-earth <650 V
Protection level wire-wire <300 V
Protection level, shield-earth (S-PE) 850 V
Protection rating IP54
Screening Indirect
Series resistance per wire 9 Ω ± 10 %
Shielding connection available yes
Signalling on device Visual
SPD to IEC 61643-21 Class I+II+III / D1+C2+C1
Telecommunications contact no
Testing standard IEC 61643-21
Total discharge current (10/350) D1: 12,5
Total discharge current (8/20) 25 kA
All types

All types

Types Number of poles Maximum continuous voltage AC Maximum continuous voltage DC Plug-in system Item no. Quantity SSU
TD-4/I 4 120 170 RJ11 5081690
1 piece
Downloads

Download

Download

Declaration of conformity TD-4/I / 5081690 , 0.15MB , pdf
Download
REACH Declaration of conformity TD-4/I / 5081690 , 0.12MB , pdf

Download
Download

TD-4/I / 5081690
Download