Note: This article is discontinued.
- Product description
-
Product description
Closed, lightning current carrying spark gap for separation of electrically conductive plant components.
• Connection bolts; Ø 10 mm; stainless steel.
• Pulsed current 50 kA (10/350)
• BET
Tested application: Installation of electrical isolations for external lightning protection and earthing systems, e.g. two earthing systems on account of mutual influence or corrosion (corrosion current prevention).
- Technical data
-
Technical data
Dimension 188x94x90 Explosion-tested version no Lightning impulse current 50 kA Nominal discharge surge current 100 kA Permitted temperature range, max. 50 °C Permitted temperature range, min. -20 °C Power frequency spark-over voltage 2,5 kV Protection level < 5,0 kV Response time <100 ns - All types
- Downloads
-
Data sheet 481 / 5240085 , 0.12MB , pdfCatalogue Überspannungsschutz , 28.42MB , pdfDeclaration of conformity 481 / 5240085 , 0.06MB , pdfMounting instructions Parex spark gap 480; 481 , 2.00MB , pdf